Products or items that are subject to Product Certification and must be used in a specific manner in order to be proven safe for use, are typically required to be installed or used in accordance with a subject-related listing, which is a document issued by an organisation that is nationally accredited for doing both testing and product certification work, in accordance with nationally accredited standards. The following is '''one example of millions of such listings''' that exist around the world for nearly countless numbers of products, such as Toaster s, Fire Extinguisher s, Fireproofing Plaster s, etc. This example is a duplicate of an Underwriters Laboratories Firestop Mortar listing based on the Fire Test depicted under the Fire-resistance Rating article. This article is also augmented with real-life photographs from the test upon which this listing was based, for better understanding. The actual certification listing includes no photographs - only text and drawings. SYSTEM NO. C-AJ-8073 1. Floor or Wall Assembly Certification Listing C-AJ-8073.]] assembly leading to UL certification listing C-AJ-8073.]]
:See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants A max of seven firestop configurations complying with Firestop Configuration A, B, C or D, and a max of four firestop configurations complying with Firestop Configuration E, F or G may be installed within the opening in any combination. The Annular Space between Penetrating Items and between penetrating items and Periphery of opening shall be as specified in the individual firestop configurations. The maximum open area within the opening shall be 480 sq in. with smaller dimension not exceeding 10 in. Pipe , Conduit , Tubing , Cable Tray or Cable to be rigidly supported on both sides of floor or wall assembly. The T Rating of the System is dependent on the firestop configuration, as shown in the table below:
Firestop Configuration A 2. Metallic Penetrants One Metal lic pipe, conduit or tubing to be installed within this firestop configuration. The annular space between pipes, conduit and tubing with a nom diam of 4 in. or less and the periphery of the opening shall be min 1/4 in. The annular space between pipes, conduit and tubing with a nom diam greater than 4 in. and the periphery of the opening shall be min 4-1/4 in. The annular space between pipes, conduit or tubing with a diam of 4 in. or less and other non-insulated penetrating items shall be min 1/2 in. The annular space between pipes, conduit and tubing with a nom diam greater than 4 in. and other non-insulated penetrating items shall be min 4-3/4 in. The following types and sizes of metallic pipes, conduits or tubing may be used:
3. Firestop System The firestop system shall consist of the following:
:Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar FIRESTOP CONFIGURATION B effect of the Copper pipe inside.]] 2. Metallic Penetrants One metallic pipe or tubing to be installed within this firestop configuration. The following types and sizes of metallic pipes or tubing may be used:
Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space between the insulated pipe or tubing and periphery of opening shall be min 6-1/2 in. The annular space between insulated pipe or tubing and other adjacent insulated penetrating items shall be min 1 in. The annular space between insulated pipe or tubing and other adjacent uninsulated penetrating items or cable trays shall be mm 5 in.
4. Firestop System The firestop system shall consist of the following:
Nom 1/4 in. thick Intumescent Elastomer ic material faced on one side with Aluminium Foil , supplied in 2 in. wide strips. One nom 2 in. wide strip tightly-wrapped around tube insulation (Item 3) with ends butted and foil side exposed, and slid into through opening such that the bottom edge is flush with bottom surface of mortar in floors or both surfaces of mortar in walls. Wrap strip held in place with pressure-sensitive tape, steel tie wire, or equivalent. :Minnesota Mining and Mfg Co. - FS-195+
Generous bead of caulk applied to Perimeter of tube insulation at its egress from the top and bottom of wrap strip. :Minnesota Mining and Mfg Co. - CP 25WB+ C. Forms - (Not Shown) - Used as a form to prevent leakage of mortar during installation. Forms to be a rigid sheet material, cut to fit the contour of the penetrating item and fastened to the underside of floor or both sides of wall. Forms to be removed after mortar has cured.
Min 3 in. thickness of mortar applied within the annulus, flush with top surface of floor or with both surfaces of wall. Cementitious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar FIRESTOP CONFIGURATION C preparation including foamed glass pipe covering for Firestop Configuration C]] ed Glass insulation is now covered with 0.015" thick Aluminium Sheet Metal and the bottom of the opening is fitted with a temporary form made of Styrofoam .]] 2. Metallic Penetrants One metallic pipe to be installed within the opening. The following types and sizes of metallic pipes may be used:
Nom 1 in. thick cellular glass units sized to the outside diam of pipe and supplied in nom 24 in. long half sections or nom 18 in. long segments. Pipe insulation installed on pipe in accordance with the manufacturer's instructions. The annular space between the insulated pipe and periphery of opening shall be min 6 in. The annular space between insulated pipe and other adjacent penetrating items shall be min 4-1/4 in.
Nom 1/4 in. diam bead of caulk applied between adjacent sections of pipe covering material at longitudinal and transverse joints. :Minnesota Mining and Mfg Co. - CP 25WB+ 5. Metal Jacket Jacket, formed of min 0.0 15 in. thick Aluminium sheet cut to wrap tightly around the pipe insulation with a min 2 in. lap and secured using min 18 gauge steel tie wire spaced 16 in. OC and nom 3/8 in. diam steel Screw s, located 1/2 in. from top of floor or both surfaces of wall. 6. Firestop System The firestop system shall consist of the following: A. Forms - (Not Shown) Used as a form to prevent leakage of mortar during installation. Forms to be a rigid sheet material, cut to fit the contour of the penetrating item and fastened to the underside of floor or both sides of wall. Forms to be removed after mortar has cured.
Min 3 in. thickness of mortar applied within the annulus, flush with top surface of floor or with both surfaces of wall. Cementitious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar FIRESTOP CONFIGURATION D 2. Metallic Penetrants One metallic pipe, conduit or tubing to be installed within the opening. The following types and sizes of metallic pipes, conduits or tubing may be used:
Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and periphery of opening shall be mm 2-1/4 in. The annular space between insulated pipe and other adjacent insulated penetrating items shall be min 1 in. The annular space between insulated pipe and other adjacent uninsulated penetrating items or cable trays shall be mm 8 in. :See Pipe and Equipment Covering - Materials (BRGU) category in the Building aterials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Firestop System The firestop system shall consist of the following:
Nom 1/4 in. thick intumescent elastomeric material faced on one side with aluminum foil, supplied in 2 in. wide strips. Two nom 2 in. wide strips tightly-wrapped around pipe covering material (Item 3) with the foil side exposed and slid into through opening such that the bottom edge is flush with bottom surface of mortar in floors or both surfaces of mortar in walls. Each layer of wrap strip to be installed with butted seam with butted seams in successive layers staggered. Wrap strip held in place with pressure-sensitive tape, steel tie wire, or equivalent. :Minnesota Mining and Mfg Co. - FS-195+
Generous bead of caulk applied to perimeter of pipe covering material at its egress from the top and bottom of wrap strip. :Minnesota Mining and Mfg Co. - CP 25WB+ C. Forms - (Not Shown) Used as a form to prevent leakage of mortar during installation. Forms to be a rigid sheet material, cut to fit the contour of the penetrating item and fastened to the underside of floor or both sides of wall. Forms to be removed after mortar has cured.
Min 3 in. thickness of mortar applied within the annulus, flush with top surface of floor or with both surfaces of wall. Cement itious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar FIRESTOP CONFIGURATION E Caulking .]] .]] assembly after it has passed the fire and hose stream tests. This is proven compatibility between the original seal and the repair method.]] Max 36 in. wide by max 6 in. deep open-ladder or solid back cable tray with channel-shaped side rails formed of galv steel and with rungs spaced 9 in. OC. The annular space between cable trays and the periphery of the opening shall be mm 0 in. (point contact) to max 10 in. The annular space between cable trays and other adjacent uninsulated penetrating items shall be min 2 in. The annular space between adjacent cable trays shall be 10 in. 3. Firestop System The firestop system shall consist of the following: A. Forms - (Not Shown) Used as a form to prevent leakage of mortar during installation. Forms to be a rigid sheet material, cut to fit the contour of the cable tray and fastened to the underside of floor or both sides of wall. Forms to be removed after mortar has cured.
Min 3 in. thickness of mortar applied within the annulus, flush with top surface of floor or with both surfaces of wall. Cementitious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar 4. Cables One cable to be centered in each of max two preformed or core-drilled openings within confines of cable tray. Diam of openings to be 1-3/8 in. Openings to be spaced min 21 in. OC and min 2-1/2 in. from back and sides of cable tray. Cables to be rigidly supported on both sides of floor or wall assembly. Any of the following types and sizes of cables may be used:
Min 3 in. thickness of caulk or putty applied within the annulus around cables, flush with top surface of floor or with both surfaces of wall. Additional caulk to be installed such that a min 1/4 in. crown is formed around the cables and at any voids between the cable trays and mortar, and between the cable trays and concrete floor or wall. :Minnesota Mining and Mfg Co. - CP 25WB+ Caulk or MPS-2+ Putty FIRESTOP CONFIGURATION F with 30PSI hose-stream.]] Max 36 in. wide by max 6 in. deep open-ladder or solid back Cable Tray with channel-shaped side rails formed of galv steel and with rungs spaced 9 in. OC. The annular space between cable trays and the periphery of the opening shall be mm 0 in. (point contact) to max 10 in. The annular space between cable trays and other adjacent uninsulated penetrating items shall be min 2 in. The annular space between adjacent cable trays shall be 10 in. 3. Firestop System The firestop system shall consist of the following: A. Forms - (Not Shown) Used as a form to prevent leakage of mortar during installation. Forms to be a rigid sheet material, cut to fit the contour of the cable tray and fastened to the underside of floor or both sides of wall. Forms to be removed after mortar has cured.
Min 3 in. thickness of mortar applied within the annulus, flush with top surface of floor or with both surfaces of wall. Cementitious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar 4. Cables One cable to be centered in each of max two preformed opening within confines of cable tray. Size of opening to be maximum 1-1/2 by 2-1/2 in. Openings to be spaced min 21 in. OC and mm 2-1/2 in. from back and sides of cable tray. Cables to be rigidly supported on both sides of floor or wall assembly. Any of the following types and sizes of cables may be used:
Min 3 in. thickness of mortar applied within the annulus around cables, flush with top surface of floor or with both surfaces of wall. Additional mortar to be installed such that a min 1/4 in. crown is formed around the cables. Cementitious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar
Min 1/4 in. bead of caulk to be installed at any voids between the cable trays and mortar, and between the cable trays and concrete floor or wall. :Minnesota Mining and Mfg Co. - CP 25WB+ FIRESTOP CONFIGURATION G being applied ''inside the Cable s first'' as this is the hardest to reach area. No forms are necessary here due to the chosen Viscosity ( Water content) of the mortar.]] Max 36 in. wide by max 6 in. deep open-ladder or solid back cable tray with channel-shaped side rails formed of aluminum and with rungs spaced 9 in. OC. The annular space between cable trays and the periphery of the opening shall be mm 0 in. (point contact) to max 10 in. The annular space between cable trays and other adjacent uninsulated penetrating items shall be min 2 in. The annular space between adjacent cable trays shall be 10 in. 3. Cables Aggregate cross-sectional area of cables in cable tray to be max 51 percent of the cross-sectional area of the cable tray. Any of the following types and sizes of cables, up to the quantity shown, may be used:
4. Firestop System The firestop system shall consist of the following: A. Forms - (Not Shown) Used as a form to prevent leakage of mortar during installation. Forms to be a rigid sheet material, cut to fit the contour of the cable tray and cables, and fastened to the underside of floor or both sides of wall. Forms to be removed after mortar has cured.
Min 3 in. thickness of mortar applied within the annulus, flush with top surface of floor or with both surfaces of wall. Additional fill material to be installed such that a min 2 in. crown is formed around the cables and lapping 2 in. beyond the cables. Cementitious mortar mixed with water at a rate of 1.0 part dry mixture to 0.3 parts water by weight in accordance with the installation instructions supplied with the product. :Minnesota Mining & Mfg Co. - 3M Fire Barrier Mortar
Caulking being applied between Cable Tray s and the opening. This gap was too small to properly fill with mortar.]] Min 1/4 in. bead of caulk to be installed at any voids between the cable trays and mortar, and between the cable trays and concrete floor or wall. :Minnesota Mining and Mfg Co. - CP 25WB+
The above is not intended to be used as a replacement for the actual listing. It is provided merely as an example of a certification listing. SEE ALSO
|
|
|