An electricity pylon or '''transmission tower''' is a tall, almost always steel lattice Structure used to Support overhead electricity conductors for Electric Power Transmission .

(the vertical string of insulators) and conductor vibration dampers (the weights attached directly onto the conductors) on a 275,000 volt suspension tower near Thornbury, South Gloucestershire, England]]

. The first tower is a tension type. The others are suspension type.]]


HIGH VOLTAGE AC TRANSMISSION PYLONS


s) for lightning protection are often added at the top of each tower.

In some countries, towers for high and extra-high voltage are usually designed to carry two or more electric circuits. For double circuit lines in Germany, the "Danube" towers or more rarely, the " Fir tree" towers, are usually used. If a line is constructed using pylons designed to carry several circuits, it is not necessary to install all the circuits at the time of construction.

Medium voltage circuits are often erected on the same towera as 110 kV lines. Paralleling circuits of 380 kV, 220 kV and 110 kV-lines on the same towers is common. Sometimes, especially with 110 kV circuits, a parallel circuit carries traction lines for railway electrification.


HISTORY


Electricity transmision towers have been used since at least the 1910s.


HIGH VOLTAGE DC TRANSMISSION PYLONS

adjacent to Dorsey Converter Station near Rosser, Manitoba — August 2005]]
High voltage Direct Current ( HVDC ) transmission lines are either Monopolar or Bipolar systems. With bipolar systems a conductor arrangement with one conductor on each side of the tower is used. For single-pole HVDC transmission with ground return, towers with only one conductor can be used. In many cases, however, the towers are designed for later conversion to a two-pole system. In these cases, conductors are installed on both sides of the tower for mechanical reasons. Until the second pole is needed, it is either grounded, or joined in parallel with the pole in use. In the latter case the line from the converter station to the earthing (grounding) electrode is built as underground cable.


RAILWAY TRACTION LINE PYLONS


Towers used for single phase AC Railway traction lines are similar in construction to those towers used for 110 kV-three phase lines. Steel tube or concrete poles are also often used for these lines. However, railway traction current systems are two-pole AC systems, so traction lines are designed for two conductors (or multiples of two, usually four, eight, or twelve). As a rule, the towers of railway traction lines carry two electric circuits, so they have four conductors. These are usually arranged on one level, whereby each circuit occupies one half of the crossarm. For four traction circuits the arrangement of the conductors is in two-levels and for six electric circuits the arrangement of the conductors is in three levels.

With limited space conditions, it is possible to arrange the conductors of one traction circuit in two levels. Running a traction power line parallel to a high voltage transmission lines for three-phase AC on a separate crossarm of the same tower is possible. If traction lines are led parallel to 380 kV-lines, the insulation must be designed for 220 kV, because in the event of a fault, dangerous overvoltages to the three-phase alternating current line can occur. Traction lines are usually equipped with one earth conductor. In Austria, on some traction circuits, two earth conductors are used.


ASSEMBLY

Lattice towers can be assembled horizontally on the ground and erected by push-pull cable, but this method is rarely used because of the large assembly area needed. Lattice towers are more usually erected using a crane or, in inaccessible areas, a helicopter.


TESTING OF MECHANICAL PROPERTIES

There are Tower Testing Station s for testing the mechanical properties of towers.


SIGN MARKINGS

anchor pylon at Dorsey Converter Station near Rosser, Manitoba — August 2005]]
in the suburb of Nizhniy Novgorod , Russia .]]
]]

Besides the obligatory high voltage warning sign, electricity towers also frequently possess a sign or circuit identification plate, with the names of the line (either the terminal points of the line or the internal designation of the EVU ) and the tower number. This makes it easier identifying the location of a fault to the power company that owns the tower.

In some countries, electricity towers of lattice steel have to be equipped with a Barbed Wire barrier approximately 3 metres above ground in order to deter unauthorized climbing. Such barriers can often be found on towers close to roads or other areas with easy public access, even where there is not such a requirement.


SPECIAL DESIGNS

Antennas for low power FM Radio , Television , and mobile phone services are sometimes erected on pylons, especially on the steel masts carrying high voltage cables.

To build branches, quite impressive constructions must occasionally be used. This also applies occasionally to twisting masts that divert three-level conductor cables.

Sometimes (in particular on steel framework pylons for the highest voltage levels) transmitting plants are installed. Usually these installations are for mobile phone services or the operating radio of the power supply firm, but occasionally also for other radio services, like directional radio. Thus transmitting antennas for low-power FM radio and television transmitters were already installed on pylons. On the carrying pylon of the Elbe Crossing 1 there is a radar facility belonging to the Hamburg water and navigation office.

For crossing broad valleys, a large distance between the conductor cables must be maintained to avoid short-circuits caused by conductor cables colliding during storms. Sometimes a separate pylon is used for each conductor. For crossing wide rivers and straits with flat coastlines very high pylons must be built, because a large height clearance is needed for navigation. Such masts must be equipped with flight safety lamps.

Two well-known crossings of wide rivers are the , Spain have a particularly interesting construction. They consist of 158-meter-high carrying pylons with one cross beam atop a frustum framework construction. The largest spans of overhead lines are the crossing of the Norwegian Sognefjord (span between two masts of 4,597 meters) and the Ameralik span in Greenland (span width: 5,376 meters). In Germany the overhead line of the EnBW AG crossing of the Eyachtal has the largest span in the country, a width of 1,444 meters.

In order to drop overhead lines into steep, deep valleys, inclined pylons are occasionally used. An example of this type of pylon is located at the Hoover Dam in the USA. In Switzerland a NOK pylon inclined around 20 degrees to the vertical is located near Sargans. Highly sloping masts are used on two 380 kV pylons in Switzerland, the top 32 meters of one of them being bent by 18 degrees to the vertical.

Power station chimneys are sometimes equipped with crossbars for fixing conductors of the outgoing lines. Because of possible problems with corrosion by the flue gases, such constructions are very rare.


TYPES OF PYLONS


Specific functions



Materials used



Conductor arrangements



Specific locations



Specific purposes